Description
Tekmar 374 Universal Reset Control - Two Mixing - Two Stage Boiler - Domestic Hot Water & Setpoint
Features:
- DHW pump or valve operation, DHW priority (optional)
- 3 Outdoor temperature reset controlled water temperatures, control up to 2 on/off boilers
- Equal run time rotation, 2 X variable speed pump outputs or 2 X floating action mixing outputs
- Quick setup for easy installation, user comfort adjustment to increase or decrease building space temperature
- Boiler load reset, automatic boiler differential
- Outdoor temperature reset, warm weather shut down
- CSA C US certified (approved to applicable UL standards)
- Advanced settings to fine-tune building requirements, test sequence to ensure proper operation
- Powered boiler system and mixing system pump outputs, exercising
Specifications:
- Agency Approvals - CSA C US, meets class B: ICES & FCC Part 15
- Ambient Conditions - Indoor use only, 32 to 122 degrees F (0 to 50 degrees C), RH less than or equal to 90 percent Non-condensing, Altitude less than 6560 ft. (2000 m), Installation Category II, Pollution Degree 2
- Control Type - Microprocessor control, this is not a safety (limit) control
- Demand - 20 to 260 V (ac) 2 VA
- Dimensions - 6-5/8" H x 7-9/16" W x 2-13/16" D (170 x 193 x 72 mm)
- Enclosure Material - Blue PVC plastic
- Enclosure NEMA Rating - NEMA 1
- Hydronic - HVAC Control Type - Universal Reset Control
- Power Supply - 115 V (ac) plus / minus 10 percent, 50/60 Hz, 1750 VA
- Variable Pump - 230 V (ac) 2.4A 1/6 hp, fuse T2.5 A 250 V
- Relay - 230 V (ac) 5 A, 1/3 hp, pilot duty 240 VA
- Zone Valve Load - 89 VA, 24 V (ac), 3.7 A for zones 1 to 4
- Sensor - NTC thermistor, 10 k ohms at 77 degrees F (25 degrees C plus / minus 0.2 degrees C) Beta=3892